Loop Isolator Module LIM

585342

Approval: EN 54-17
Loop Isolator Module to install a short-circuit and open-circuit tolerant 100 V loudspeaker loop wiring system in VARIODYN ONE loop technology. The modules monitor the current on the loudspeaker loop and disconnect the defective part of the loop in case of over-current, e.g. at a short-circuit. Loop failures are displayed on VARODYN INC (Intelligent Network Controller) and PACT-software. Each module has a total of three two-pole terminals to connect the loop wiring system and the speakers. Wires with a cross-section of up to 2.5 mm² can be connected to the terminals. In addition, each LIM has 3 LEDs to display the operating status. The LIM is housed in a stable, compact IP 66 housing with sufficient wiring space and can be used in projects with difficult environmental conditions, e.g. in industrial applications.




Isolator-Modul zum Aufbau einer kurzschluss- und drahtbruchtoleranten 100-V-Lautsprecher-Ringverdrahtung in VARIODYN ONE-Ringleitungstechnik. Die Module überwachen den Strom auf dem Lautsprecherring und trennen bei Überstrom, z.B. im Falle eines Kurzschlusses, den kurzgeschlossenen Teil aus dem Ring. Ringleitungsstörungen werden am INC (Intelligent Network Controller) und in der PACT-Software angezeigt. Jedes Modul verfügt über insgesamt drei zweipolige Klemmen zum Anschluss des Ringleitungssystems und der Lautsprecher. An die Klemmen können Leitungen mit einem Querschnitt von bis zu 2,5 mm² angeschlossen werden. Des Weiteren sind an jedem Modul 3 LEDs zur Anzeige des Betriebszustands vorhanden. Das Loop-Isolator-Modul ist in einem stabilen, kompakten IP 66-Gehäuse mit ausreichend Verkabelungsraum untergebracht und kann in Projekten mit schwierigen Umgebungsbedingungen, z.B. im industriellen Einsatz, eingesetzt werden.
Isolator-Modul zum Aufbau einer kurzschluss- und drahtbruchtoleranten 100-V-Lautsprecher-Ringverdrahtung in VARIODYN ONE-Ringleitungstechnik. Die Module überwachen den Strom auf dem Lautsprecherring und trennen bei Überstrom, z.B. im Falle eines Kurzschlusses, den kurzgeschlossenen Teil aus dem Ring. Ringleitungsstörungen werden am INC (Intelligent Network Controller) und in der PACT-Software angezeigt. Jedes Modul verfügt über insgesamt drei zweipolige Klemmen zum Anschluss des Ringleitungssystems und der Lautsprecher. An die Klemmen können Leitungen mit einem Querschnitt von bis zu 2,5 mm² angeschlossen werden. Des Weiteren sind an jedem Modul 3 LEDs zur Anzeige des Betriebszustands vorhanden. Das Loop-Isolator-Modul ist in einem stabilen, kompakten IP 66-Gehäuse mit ausreichend Verkabelungsraum untergebracht und kann in Projekten mit schwierigen Umgebungsbedingungen, z.B. im industriellen Einsatz, eingesetzt werden.
Loop Isolator Module to install a short-circuit and open-circuit tolerant 100 V loudspeaker loop wiring system in VARIODYN ONE loop technology. The modules monitor the current on the loudspeaker loop and disconnect the defective part of the loop in case of over-current, e.g. at a short-circuit. Loop failures are displayed on VARODYN INC (Intelligent Network Controller) and PACT-software. Each module has a total of three two-pole terminals to connect the loop wiring system and the speakers. Wires with a cross-section of up to 2.5 mm² can be connected to the terminals. In addition, each LIM has 3 LEDs to display the operating status. The LIM is housed in a stable, compact IP 66 housing with sufficient wiring space and can be used in projects with difficult environmental conditions, e.g. in industrial applications.
  • Increased safety compared to spur cabling
  • Fully redundant 100 V loop wiring system technology
  • Extensive topologies are possible
  • Short-circuit and wire break tolerant
  • EN 54-17 certified
  • Large saving in wiring and installation

Additional Information:
Please consider that the amplifier 4XD125B (585030) and 4XD250B (585031) are not compatible with the loop technology!

Operating voltage 24 V DC
Current consumption
1 mA (fast charge current 10 mA max.)
Ambient temperature
-5 °C ... 55 °C
Storage temperature
-40 °C ... 70 °C
Air humidity
< 95 % (non-condensing)
Maximum line voltage
100 Vrms AC or 30 V DC
Maximum line voltage (without a short circuit or partial short circuit fault)
20 V DC
Maximum rated continuous current with the switch closed
6 A
Maximum rated switching current (under short circuit)
6 A
Maximum series impedance with the switch closed (ZC max.)
< 100 mΩ
Weight
approx. 130 g
Dimensions W: 114 mm H: 114 mm D: 57 mm
Threshold for LIM Enablement / Disablement
Line voltage difference <1V /Line voltage difference >1V and reset signal is received