Infrared Methane Detector in ATEX Box

E700IR-2

The detector is equipped with an infrared detection system capable of distinguishing other types of gas, thus ensuring a perfect selectivity. It measures the concentration of the explosive gas on the LEL (Lower Explosive Limit) scale. The detector is delivered with a pre-alarm threshold of 15% and an alarm threshold of 30% of the LEL.Optionally, an interface with Android App and a PC software are available, which allow the field testing of the detector, and the modification of detection thresholds, alarm filters, addressing, full scale, etc. The detector is equipped with an ATEX II 2G Ex-d IIC T6 Gb certified explosionproof metal box, housing both the communication electronics and the sensor element, and protected by a sintered filter in a resin-coated steel box.
  • Multiple communication modules for all kinds of applications
  • Easy replacement of sensor element in case of depletion or failure
  • ATEX II 2G Ex-d IIC T6 Gb certified explosion-proof metal box
  • Optionally configuration via Android App and PC software
  • Direct connection with ESSER by Honeywell loop transponder
  • Modbus Interface for communication to management systems
Supply voltage
12/24 Vdc
Detection type (pre-heating of 150”)
Infrared
Service life in optimal conditions
5 years
Current consumption in standby mode
max. 90 mA
Current consumption in alarm mode
max. 110 mA
Operating temperature
0 °C / +50 °C
Treshold
0-100% LEL
Resolution
0.05 up to 5%
Linearity readout
±5%
Precision readout @ 20 °C
±5%
Gas response time T90
< 30 seconds
Box
ATEX Exd ADPE
Weight
1000g
Dimensions HxWxD (mm)
165 x 90 x 80
Coverage on installation
approx. 5 meters
Certification
ATEX II 2G Ex-d IIC T6 Gb
  • Since the detectors will be pre-assembled with the communication module, please indicate in your order with two separate lines next to each other the detector type and the related communication module quantity needed.
  • ES1-L7 ESSER by Honeywell Interface: absorption output module
  • ES2-L7 ESSER by Honeywell Interface: output module with O.C. opto-isolated NPN
  • ES3-L7 ESSER by Honeywell Interface: 3 relay output module for fault, pre-alarm, alarm
  • G7-42 Analog output module at 4-20 mA
  • G7-RL4 4 relay output module
  • G7-MB Modbus output module