Like article 762251 but with additional stainless steel braiding (min. 70% coverage) over PVC outer jacket. Suitable for increased mechanical strength and abrasion resistance. Suitable for indoor and outdoor use. Can be exposed to direct sunlight to a limited extent. Not suitable for (potential) contact with aggressive chemicals.
The sensor cable must be fixed below ceiling areas at least every 50cm. The distance to cold ceiling areas must be at least 2 cm.