Basic unit TITANUS TOP SENS® EB

801531.10

Approval: VdS, FM

Basic unit for wall mounting, ready for receiving a detector module DM-TT-xx. It is provided with three alarm levels for information alarm, pre-alarm and main alarm as well as with a bargraph display to indicate the specific smoke density level. Titanus Top Sens EB can be directly connected to the esserbus / esserbus PLus.
The device is supplied with front foil for single-tube operation.
  • Pre-configured for usage with DM-TT-xx detector module
  • Optical status display for information alarm, pre-alarm, main alarm and fault indication
  • Integrated bar graph display to optically indicate the current smoke level
  • Ports for two suction tubes with outside diameter of 25 mm
  • Port for air return pipe

Additional Information:
Isolator not included with delivery, can be optionally ordered under Part No. 788612.

Scope of Delivery:
Pre-configured basic device including esserbus transponder and reset PC board as well as the front foil.
Alarm displayred LED
Alarm current @ 24 V DC230 mA ... 290 mA (w/o reset PCB)
Starting current @ 24V DC (w/o reset PCB)300 mA (w/o reset PCB)
Connecting cable(recommended) pair-wired, screened e.g. I-Y(St)Y n x 2 x 0,8 mm
Connection terminalmax. 1,5 mm²
Operation indicatorgreen LED
Operating voltage14 ... 30 V DC
Colorwhite, similar to RAL 9018
HousingABS plastic
Weight kg approx. 1.35 kg
Cable entry5 x M 20 / 2 x M 25
Beveled tubular plug2 x for ABS tube D=25 mm for return air duct D=25 mm
Contact load relay30 V DC/1 A max. 24 W
Storage temperature-25 °C ... 65 °C
Exhauster life time (12V)43.500 h at 24°C
Air humidity< 95 % (non-condensing)
Quiescent current @ 24 V DCapprox. 260 mA @ 9 V fan voltage
Type of protectionIP20 (IP52 with optional sealing kit)
Fault displayyellow LED
Ambient temperature-20 °C ... 60 °C
VdS classF
VdS-NrG 206118
DimensionsW: 200 mm H: 292 mm D: 113 mm