Fireray 50 RV with 1 prism
VEA-040-A00
Approval: VdS
The detector consists of an integrated infrared transmitter and receiver. The signal is reflected by a prism and analyzed by the receiving element. Signal reaching the threshold will trigger an alarm.
Integration on the loop and the resetting function is carried out via the esserbus transponder 808623.
Integration on conventional line requires use of a reset module. The detector requires a separate voltage supply of 24 V DC.
The Fireray is installed approx. 0.3 to 0.8 m underneath the ceiling and its reflector with the same ceiling distance opposite. There should be no reflecting obstacles in the transmission zone (approx. 2 degrees).