IQ8Alarm Plus/So Sounder, red

807205R

Addressable, completely bus supplied and short circuit / open circuit resilient fire alarm sounder in compliance with EN 54‑3 with integrated signaling tones for acoustic alarm signaling.
With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.
The volume can be set to 8 different levels. The load factor can be set to 2 different levels.
Signaling device with flat base, suitable for wall and ceiling mounting.
Optionally, IP base Part No. 806202 with side cable entry and weatherproof protection can be installed.

Addressable, completely bus supplied and short circuit / open circuit resilient fire alarm sounder in compliance with EN 54‑3 with integrated signaling tones for acoustic alarm signaling.

With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.

The volume can be set to 8 different levels. The load factor can be set to 2 different levels.

Signaling device with flat base, suitable for wall and ceiling mounting.

Optionally, IP base Part No. 806202 with side cable entry and weatherproof protection can be installed.

  • Completely bus supplied alarm device
  • Powered loop compatible
  • Low power consumption
  • Up to 64 alarm devices for each powered loop
  • Each alarm device has built-in isolator
  • Synchronous trigger
Acoustic alarm properties:
  • EN 54-3 compliant
  • High acoustic pressure
  • Volume programmable in 8 steps via tools 8000
  • 20 different signaling tones, including DIN tone

Additional Information:
Replacement for Part No. 807206

Common technical data:


Quiescent current @ 19 V DC
approx. 55 μA
Quiescent current @ FACP battery
approx. 300 μA @ 42 V
Declaration of Performance
DoP-21430171215
Ambient temperature
-10 °C ... 55 °C
Storage temperature
-25 °C ... 75 °C
Type of protection
IP 43*2
IP 56 with IP base 806202*3
Housing
Polycarbonate plastic
Air humidity
< 95 % (non-condensing)
Color
red, similar to RAL 3020
Weight
approx. 300 g (with base)
Operating voltage
8 ... 42 V DC (via powered loop)
Dimensions
Ø: 112 mm D: 78 mm
Ø: 112 mm D: 93 mm (with IP base)
Operating voltage
8 ... 42 V DC (via powered loop)

Acoustic:

Load factor acoustic
1,5 *1 / 3
Sound level
91 *1 / 97 dB (A) +/- 2 dB @ 1 m / @ 90° angle / @ DIN Tone
Specification
EN 54-3: 2001 / A1: 2002 / A2 : 2006 / -17: 2005
EN 54-3 Sounder

*1 Factory setting, configuration with service- and programming software tools 8000
*2 IP 21C acc. EN 54-3 / -23
*3 Do not use the base for acoustic alarm applications in compliance with EN 54-3

  • 806202 IP65 base, red